Skip to content
SA Protection Series current transformer — general arrangement SA Protection Series current transformer — dimensioned drawing
Protection CT SA-PRO

SA Protection Series

Protection class CTs that hold their ratio through fault current so relays see a faithful signal.

Product Code
SA-PRO
Primary Current
100A – 10000A
Secondary Current
5A or 1A
Accuracy Class
5P10 / 5P20
Burden
5.0 – 15 VA
Inner Diameter
Window or bar primary

Made to your specification

Specify the relay, its burden and the required accuracy limit factor and the core will be sized accordingly.

Description

The SA protection series is wound for accuracy limit performance rather than metering precision. The core is sized so the transformer keeps transforming during a fault instead of saturating, which is what allows a relay to discriminate correctly.

Accuracy limit factor and burden are matched to the relay being fed, so specify the relay model along with the ratio when enquiring.

Features

  • Core sized against saturation under fault
  • Accuracy limit factor matched to the relay
  • Window or bar primary construction
  • Suitable for overcurrent and earth fault schemes

Applications

  • Overcurrent protection schemes
  • Earth fault detection
  • Feeder and motor protection

Technical specifications

Technical specifications for SA Protection Series
Product Code SA-PRO
Primary Current 100A – 10000A
Secondary Current 5A or 1A
Accuracy Class 5P10 / 5P20
Burden 5.0 – 15 VA
Inner Diameter Window or bar primary
Frequency 50 / 60 Hz
Insulation 720 V, Class B
Mounting Type Busbar or base mounted
Application Overcurrent and earth fault protection

Values shown are for the standard build. Ratio, burden, accuracy class and aperture can be changed to order.

Request a quote

Enquire about the SA Protection Series

The product is preselected below. Add the ratio, burden and quantity you need and you will get a quotation with a firm lead time.

Your details
Requirement

Include the meter or relay being fed if you know it.

Fields marked * are required. Your details are used only to answer this enquiry.

Related products

View all products
SA3RH20 Compact Nylon Cased CT

SA3RH20

Compact nylon cased ring CT with a 20 mm aperture, sized for retrofit into existing metering panels.

Ratio
30A ,40A ,50A,60A, 80A, 100A / 5A & 1A
Accuracy
Class 1.0
Inner Dia.
20MM
SA3R20 Compact Nylon Cased CT

SA3R20

Compact nylon cased ring CT with a 20 mm aperture, sized for retrofit into existing metering panels.

Ratio
50A – 400A / 5A
Accuracy
Class 1.0
Inner Dia.
20 mm
SA3W Tape Wound CT

SA3W

Tape wound toroidal CT supplied with flying leads, built around your mechanical envelope.

Ratio
100A – 1000A / 5A or 1A
Accuracy
Class 1.0
Inner Dia.
25 mm and above